Direct On Line Starter
Direct On Line Starter
Introduction:
- Different
starting methods are employed for starting induction motors because
Induction Motor draws more starting current during starting. To prevent
damage to the windings due to the high starting current flow, we employ
different types of starters.
- The
simplest form of motor starter for the induction motor is the Direct On Line starter. The DOL
starter consist a MCCB or Circuit Breaker, Contactor and an overload relay
for protection. Electromagnetic contactor which can be opened by the
thermal overload relay under fault conditions.
- Typically,
the contactor will be controlled by separate start and stop buttons, and
an auxiliary contact on the contactor is used, across the start button, as
a hold in contact. I.e. the contactor is electrically latched closed while
the motor is operating.
Principle of DOL:
- To
start, the contactor is closed, applying full line voltage to the motor
windings. The motor will draw a very high inrush current for a very short
time, the magnetic field in the iron, and then the current will be limited
to the Locked Rotor Current of the motor. The motor will develop Locked Rotor
Torque and begin to accelerate towards full speed.
- As the
motor accelerates, the current will begin to drop, but will not drop
significantly until the motor is at a high speed, typically about 85% of
synchronous speed. The actual starting current curve is a function of the
motor design, and the terminal voltage, and is totally independent of the
motor load.
- The
motor load will affect the time taken for the motor to accelerate to full
speed and therefore the duration of the high starting current, but not the
magnitude of the starting current.
- Provided
the torque developed by the motor exceeds the load torque at all speeds
during the start cycle, the motor will reach full speed. If the torque
delivered by the motor is less than the torque of the load at any speed
during the start cycle, the motor will stops accelerating. If the starting
torque with a DOL starter is insufficient for the load, the motor must be
replaced with a motor which can develop a higher starting torque.
- The
acceleration torque is the torque developed by the motor minus the load
torque, and will change as the motor accelerates due to the motor speed
torque curve and the load speed torque curve. The start time is dependent
on the acceleration torque and the load inertia.
- DOL starting have a maximum start current
and maximum start torque. This may cause an electrical
problem with the supply, or it may cause a mechanical problem with the
driven load. So this will be inconvenient for the users of the supply line,
always experience a voltage drop when starting a motor. But if this motor
is not a high power one it does not affect much.
Parts of DOL Starters:
(1) Contactors & Coil.
- Magnetic
contactors are electromagnetically operated switches that provide a safe
and convenient means for connecting and interrupting branch circuits.
- Magnetic
motor controllers use electromagnetic energy for closing switches. The
electromagnet consists of a coil of wire placed on an iron core. When a
current flow through the coil, the iron of the magnet becomes magnetized,
attracting an iron bar called the armature. An interruption of the current
flow through the coil of wire causes the armature to drop out due to the
presence of an air gap in the magnetic circuit.
- Line-voltage
magnetic motor starters are electromechanical devices that provide a safe,
convenient, and economical means of starting and stopping motors, and have
the advantage of being controlled remotely. The great bulk of motor
controllers sold are of this type.
- Contactors
are mainly used to control machinery which uses electric motors. It
consists of a coil which connects to a voltage source. Very often for
Single phase Motors, 230V coils are used and for three phase motors, 415V
coils are used. The contactor has three main NO contacts and lesser power
rated contacts named as Auxiliary Contacts [NO and NC] used for the
control circuit. A contact is conducting metal parts which completes or
interrupt an electrical circuit.
- NO-normally
open
- NC-normally
closed
(2) Over Load Relay (Overload
protection).
- Overload
protection for an electric motor is necessary to prevent burnout and to
ensure maximum operating life.
- Under
any condition of overload, a motor draws excessive current that causes
overheating. Since motor winding insulation deteriorates due to
overheating, there are established limits on motor operating temperatures
to protect a motor from overheating. Overload relays are employed on a
motor control to limit the amount of current drawn.
- The overload relay does not
provide short circuit protection. This is the function of over current
protective equipment like fuses and circuit breakers, generally located in
the disconnecting switch enclosure.
- The
ideal and easiest way for overload protection for a motor is an element
with current-sensing properties very similar to the heating curve of the
motor which would act to open the motor circuit when full-load current is
exceeded. The operation of the protective device should be such that the
motor is allowed to carry harmless over-loads but is quickly removed from
the line when an overload has persisted too long.
- Normally
fuses are not designed to provide overload protection. Fuse is protecting
against short circuits (over current protection). Motors draw a high
inrush current when starting and conventional fuses have no way of
distinguishing between this temporary and harmless inrush current and a
damaging overload. Selection of Fuse is depend on motor full-load current,
would “blow” every time the motor is started. On the other hand, if a fuse
were chosen large enough to pass the starting or inrush current, it would
not protect the motor against small, harmful overloads that might occur later.
- The
overload relay is the heart of motor protection. It has inverse-trip-time
characteristics, permitting it to hold in during the accelerating period
(when inrush current is drawn), yet providing protection on small
overloads above the full-load current when the motor is running. Overload
relays are renewable and can withstand repeated trip and reset cycles
without need of replacement. Overload relays cannot, however, take the
place of over current protection equipment.
- The
overload relay consists of a current-sensing unit connected in the line to
the motor, plus a mechanism, actuated by the sensing unit, which serves,
directly or indirectly, to break the circuit.
- Overload
relays can be classified as being thermal, magnetic, or electronic.
- Thermal Relay: As the name
implies, thermal overload relays rely on the rising temperatures caused by
the overload current to trip the overload mechanism. Thermal overload
relays can be further subdivided into two types: melting alloy and
bimetallic.
- Magnetic Relay: Magnetic
overload relays react only to current excesses and are not affected by
temperature.
- Electronic Relay:
Electronic or solid-state overload relays, provide the combination of
high-speed trip, adjustability, and ease of installation. They can be
ideal in many precise applications.
Wiring of DOL Starter:
(1) Main Contact:
- Contactor
is connecting among Supply Voltage, Relay Coil and Thermal Overload Relay.
- L1 of
Contactor Connect (NO) to R Phase through MCCB
- L2 of
Contactor Connect (NO) to Y Phase through MCCB
- L3 of
Contactor Connect (NO) to B Phase through MCCB.
- NO Contact (-||-):
- (13-14
or 53-54) is a normally Open NO contact (closes when the relay energizes)
- Contactor
Point 53 is connecting to Start Button Point (94) and 54 Point of
Contactor is connected to Common wire of Start/Stop Button.
- NC Contact (-|/|-):
- (95-96)
is a normally closed NC contact (opens when the thermal overloads trip if
associated with the overload block)
(2) Relay Coil Connection:
- A1 of
Relay Coil is connecting to any one Supply Phase and A2 is connecting to
Thermal over Load Relay’s NC Connection (95).
(3) Thermal Overload Relay
Connection:
- T1,T2,T3
are connect to Thermal Overload Relay
- Overload
Relay is Connecting between Main Contactor and Motor
- NC
Connection (95-96) of Thermal Overload Relay is connecting to Stop Button
and Common Connection of Start/Stop Button.
Wiring Diagram of DOL Starter:
Working of DOL Starter:
- The
main heart of DOL starter is Relay Coil. Normally it gets one phase
constant from incoming supply Voltage (A1).when Coil gets second Phase
relay coil energizes and Magnet of Contactor produce electromagnetic field
and due to this Plunger of Contactor will move and Main Contactor of
starter will closed and Auxiliary will change its position NO become NC
and NC become (shown Red Line in Diagram) .
- Pushing Start Button:
- When
We Push the start Button Relay Coil will get second phase from Supply
Phase-Main contactor(5)-Auxiliary Contact(53)-Start button-Stop
button-96-95-To Relay Coil (A2).Now Coil energizes and Magnetic field
produce by Magnet and Plunger of Contactor move. Main Contactor closes and
Motor gets supply at the same time Auxiliary contact become (53-54) from
NO to NC .
- Release Start Button:
- Relay
coil gets supply even though we release Start button. When We release
Start Push Button Relay Coil gets Supply phase from Main contactor
(5)-Auxiliary contactor (53) – Auxiliary contactor (54)-Stop
Button-96-95-Relay coil (shown Red / Blue Lines in Diagram).
- In
Overload Condition of Motor will be stopped by intermission of Control
circuit at Point 96-95.
- Pushing Stop Button:
- When
we push Stop Button Control circuit of Starter will be break at stop
button and Supply of Relay coil is broken, Plunger moves and close contact
of Main Contactor becomes Open, Supply of Motor is disconnected.
Motor Starting Characteristics on
DOL Starter:
- Available
starting current: 100%.
- Peak
starting
current: 6
to 8 Full Load Current.
- Peak
starting
torque: 100%
Advantages of DOL Starter:
- Most
Economical and Cheapest Starter
- Simple
to establish, operate and maintain
- Simple
Control Circuitry
- Easy
to understand and trouble‐shoot.
- It
provides 100% torque at the time of starting.
- Only
one set of cable is required from starter to motor.
- Motor
is connected in delta at motor terminals.
Disadvantages of DOL Starter:
- It
does not reduce the starting current of the motor.
- High Starting Current:
Very High Starting Current (Typically 6 to 8 times the FLC of the motor).
- Mechanically Harsh:
Thermal Stress on the motor, thereby reducing its life.
- Voltage Dip: There is a
big voltage dip in the electrical installation because of high in-rush
current affecting other customers connected to the same lines and
therefore not suitable for higher size squirrel cage motors
- High starting Torque:
Unnecessary high starting torque, even when not required by the load,
thereby increased mechanical stress on the mechanical systems such as
rotor shaft, bearings, gearbox, coupling, chain drive, connected
equipments, etc. leading to premature failure and plant downtimes.
Features of DOL starting
- For
low- and medium-power three-phase motors
- Three
connection lines (circuit layout: star or delta)
- High
starting torque
- Very
high mechanical load
- High
current peaks
- Voltage
dips
- Simple
switching devices
DOL is Suitable for:
- A direct
on line starter can be used if the high inrush current of the motor does
not cause excessive voltage drop in the supply circuit. The maximum size
of a motor allowed on a direct on line starter may be limited by the
supply utility for this reason. For example, a utility may require rural
customers to use reduced-voltage starters for motors larger than 10 kW.
- DOL
starting is sometimes used to start small water pumps, compressors, fans
and conveyor belts.
DOL is not suitable for:
- The
peak starting current would result in a serious voltage drop on the supply
system
- The
equipment being driven cannot tolerate the effects of very high peak
torque loadings
- The
safety or comfort of those using the equipment may be compromised by
sudden starting as, for example, with escalators and lifts.
No comments:
Post a Comment