Electrical Bus System & Substation Layout
Electrical Bus System
There are many different electrical bus system schemes available but
selection of a particular scheme depends upon the system voltage,
position of substation in electrical power system, flexibility needed in
system and cost to be expensed.
The main criteria’s to be considered during selection of one particular Bus – Bar Arrangement Scheme among others
(i) Simplicity of system
(ii) Easy maintenance of different equipments.
(iii) Minimizing the outage during maintenance.
(iv) Future provision of extension with growth of demand
(v) Optimizing the selection of bus bar arrangement scheme so that it gives maximum return from the system.
Some very commonly used bus bar arrangement are discussed below
Single Bus System
Single Bus System is simplest and cheapest one. In this scheme all
the feeders and transformer bay are connected to only one single bus as
shown.
Advantages of single bus system
This is very simple in design
This is very cost effective scheme
This is very convenient to operate
Disadvantages of single bus system
![Single Bus System single bus system](http://www.electrical4u.com/images/single-bus-system.gif)
One but major difficulty of these type of arrangement is that,
maintenance of equipment of any bay cannot be possible without
interrupting the feeder or transformer connected to that bay.
The indoor 11KV switchboards have quite often single bus bar arrangement.
Single Bus System with Bus Sectionalizer
Some advantages are realized if a single bus bar is sectionalized
with circuit breaker. If there are more than one incoming and the
incoming sources and outgoing feeders are evenly distributed on the
sections as shown in the figure, interruption of system can be reduced
to a good extent.
Advantages of single bus system with bus sectionalizer
If any of the sources is out of system, still all loads can be fed by
switching on the sectional circuit breaker or bus coupler breaker.
![Single Section Bus System single section bus system](http://www.electrical4u.com/images/single-section-bus-system.gif)
If one section of the bus bar system is under maintenance, part load of
the substation can be fed by energizing the other section of bus bar.
Disadvantages of single bus system with bus sectionalizer
As in the case of single bus system, maintenance of equipment of any
bay cannot be possible without interrupting the feeder or transformer
connected to that bay.
The use of isolator for bus sectionalizing does not fulfill the
purpose. The isolators have to be operated ‘off circuit’ and which is
not possible without total interruption of bus – bar. So investment for
bus-coupler breaker is required.
Double Bus System
In double bus bar system two identical bus bars are used in such a
way that any outgoing or incoming feeder can be taken from any of the
bus.
Actually every feeder is connected to both of the buses in parallel
through individual isolator as shown in the figure.
![Double Bus System double bus system](http://www.electrical4u.com/images/double-bus-system.gif)
By closing any of the isolators one can put the feeder to associated
bus. Both of the buses are energized and total feeders are divided into
two groups, one group is fed from one bus and other from other bus. But
any feeder at any time can be transferred from one bus to other. There
is one bus coupler breaker which should be kept close during bus
transfer operation. For transfer operation, one should first close the
bus coupler circuit breaker then close the isolator associated with the
bus to where the feeder would be transferred and then open the isolator
associated with the bus from where feeder is transferred. Lastly after
this transfer operation he or she should open the bus coupler breaker.
Advantages of Double Bus System
Double Bus Bar Arrangement increases the flexibility of system.
Disadvantages of Double Bus System
The arrangement does not permit breaker maintenance with out interruption.
Double Breaker Bus System
![Double Breaker Bus System double breaker bus system](http://www.electrical4u.com/images/double-breaker-bus-system.gif)
In double breaker bus bar system two identical bus bars are used in
such a way that any outgoing or incoming feeder can be taken from any of
the bus similar to double bus bar system. Only difference is that here
every feeder is connected to both of the buses in parallel through
individual breaker instead only isolator as shown in the figure. By
closing any of the breakers and its associated isolators, one can put
the feeder to respective bus. Both of the buses are energized and total
feeders are divided into two groups, one group is fed from one bus and
other from other bus similar to previous case. But any feeder at any
time can be transferred from one bus to other. There is no need of bus
coupler as because the operation is done by breakers instead of
isolator. For transfer operation, one should first close the isolators
and then the breaker associated with the bus to where the feeder would
be transferred and then he or she opens the breaker and then isolators
associated with the bus from where feeder is transferred.
One and a half Breaker Bus System
![One and Half Breaker Bus System one and half breaker bus system](http://www.electrical4u.com/images/one-and-half-breaker-bus-system.gif)
This is an improvement on the double breaker scheme to effect saving
in the number of circuit breakers. For every two circuits only one spare
breaker is provided. The protection is however complicated since it
must associate the central breaker with the feeder whose own breaker is
taken out for maintenance. For the reasons given under double breaker
scheme and because of the prohibitory costs of equipment even this
scheme is not much popular. As shown in the figure that it is a simple
design, two feeders are fed from two different buses through their
associated breakers and these two feeders are coupled by a third breaker
which is called tie breaker. Normally all the three breakers are closed
and power is fed to both the circuits from two buses which are operated
in parallel. The tie breaker acts as coupler for the two feeder
circuits.
During failure of any feeder breaker, the power is fed through the
breaker of the second feeder and tie breaker, therefore each feeder
breaker has to be rated to feed both the feeders, coupled by tie
breaker.
Advantages of One and a half Breaker Bus System
During any fault on any one of the buses, that faulty bus will be
cleared instantly without interrupting any feeders in the system since
all feeders will continue to feed from other healthy bus.
Disadvantages of One and a half Breaker Bus System
This scheme is much expensive due to investment for third breaker.
Main and Transfer Bus System
![Main and Transfer Bus System main and transfer bus system](http://www.electrical4u.com/images/transfer-bus-system.gif)
This is an alternative of double bus system. The main conception of
Main and Transfer Bus System is, here every feeder line is directly
connected through an isolator to a second bus called transfer bus. The
said isolator in between transfer bus and feeder line is generally
called bypass isolator. The main bus is as usual connected to each
feeder through a bay consists of circuit breaker and associated
isolators at both side of the breaker. There is one bus coupler bay
which couples transfer bus and main bus through a circuit breaker and
associated isolators at both sides of the breaker. If necessary the
transfer bus can be energized by main bus power by closing the transfer
bus coupler isolators and then breaker. Then the power in transfer bus
can directly be fed to the feeder line by closing the bypass isolator.
If the main circuit breaker associated with feeder is switched off or
isolated from system, the feeder can still be fed in this way by
transferring it to transfer bus.
Switching operation for transferring a feeder to transfer bus from main bus without interruption of power
(i) First close the isolators at both side of the bus coupler breaker.
(ii) Then close the bypass isolator of the feeder which is to be transferred to transfer bus.
(iii) Now energized the transfer bus by closing the bus coupler circuit breaker from remote.
(iv) After bus coupler breaker is closed, now the power from main bus
flows to the feeder line through its main breaker as well as bus
coupler breaker via transfer bus.
(v) Now if main breaker of the feeder is switched off, total power
flow will instantaneously shift to the bus coupler breaker and hence
this breaker will serve the purpose of protection for the feeder.
(vi) At last the operating personnel open the isolators at both sides
of the main circuit breaker to make it isolated from rest of the live
system.
So it can be concluded that in Main & Transfer Bus System the
maintenance of circuit breaker is possible without any interruption of
power. Because of this advantage the scheme is very popular for 33KV
and 13KV system.
Double Bus System with Bypass Isolators
![Double Bus with Bypass Isolator System double bus with bypass isolator system](http://www.electrical4u.com/images/double-bus-with-bypass-isol.gif)
This is combination of the double bus system and main and transfer
bus system. In Double Bus System with Bypass Isolators either bus can
act as main bus and second bus as transfer bus. It permits breaker
maintenance without interruption of power which is not possible in
double bus system but it provides all the advantages of double bus
system. It however requires one additional isolator (bypass isolator)
for each feeder circuit and introduces slight complication in system
layout. Still this scheme is best for optimum economy of system and it
is best optimum choice for 220KV system.
Ring Bus System
![Ring Bus System ring bus system](http://www.electrical4u.com/images/ring-bus-system.gif)
The schematic diagram of the system is given in the figure. It
provides a double feed to each feeder circuit, opening one breaker under
maintenance or otherwise does not affect supply to any feeder. But this
system has two major disadvantages. One as it is closed circuit system
it is next to impossible to extend in future and hence it is unsuitable
for developing system. Secondly, during maintenance or any other reason
if any one of the circuit breaker in ring loop is switch of reliability
of system becomes very poor as because closed loop becomes opened.
Since, at that moment for any tripping of any breaker in the open loop
causes interruption in all the feeders between tripped breaker and open
end of the loop.
No comments:
Post a Comment